fbpx

    Logo

    facebook linklinkedinyoutube

    Order Online

    Selecting a RegO Regulator

    In order to properly size the RegO® Regulator, find the total load of the installation. The total load is calculated by adding up the input ratings (BTU or CFH) of all appliances in the installation. Input ratings may be obtained from the nameplates on the appliances or from the manufacturers' literature.

    TYPE OF SYSTEMMAXIMUM LOADSuggested Regulator
    First Stage in a Two Stage System 1,500,000 LV3403TR
    2,500,000 LV4403SR Series
    LV4403TR Series
    Second Stage in a Two Stage System 450,000 LV3403B Series
    935,000 LV4403B Series
    1,600,000 LV5503B4/B6
    2,300,000 LV5503B8
    9,800,000 LV6503B Series
    Second Stage in a 2 PSIG System 1,000,000 LV4403Y4/Y46R
    2,200,000 LV5503Y6/Y8
    Integral Twin Stage 450,000 LV404B34/39 Series
    525,000 LV404B4/B9 Series
    800,000 LV404Y9
    Automatic Changeover 200,000 7525B34
    450,000 7525B4

    Determine the type of regulation needed referring to the chart below.

    Now determine which regulator in the Series would be most suitable. Turn to the individual product pages and refer to the Performance Curves. Check the performance of the regulator with your actual load conditions at the minimum LP-Gas inlet pressure for the regulator. Use the pressure corresponding to your lowest winter temperatures shown in the chart below or refer to the delivery pressure of your first stage regulator.

    TEMPERATUREAPPROX. PRESSURE (PSIG)
    °F°CPROPANEBUTANE
    -40 -40 3.6 NA
    -30 -34 8 NA
    -20 -29 13.5 NA
    -10 -23 23.3 NA
    0 -18 28 NA
    10 -12 37 NA
    20 -7 47 NA
    30 -1 58 NA
    40 4 72 3.0
    50 10 86 6.9
    60 16 102 12
    70 21 127 17
    80 27 140 23
    90 32 165 29
    100 38 196 36
    110 43 220 45

    Example for a First Stage Regulator

    1. Assume a load of 500,000 BTU's per hour.
    2. Assume a minimum delivery pressure of 9.5 PSIG.
    3. Assume a minimum tank pressure of 15 PSIG.
    4. For these conditions, refer to chart for the LV4403TR Series, First Stage Regulator, shown below.
    5. Find the line on the chart corresponding to the lowest anticipated winter tank pressure (note that each performance line corresponds to and is marked with a different inlet pressure in PSIG).
    6. Draw a vertical line upward from the point of assumed load (500,000 BTU's per hour) to intersect with the line corresponding to the lowest tank pressure.
    7. Read horizontally from the intersection of these lines to the delivery pressure at the left side of the chart. In this example the delivery pressure will be 9.7 PSIG. Since the delivery pressure will be 9.7 PSIG at the maximum load conditions and lowest anticipated tank pressure, the regulator will be sized properly for the demand.

    First stage regulator delivery pressure PSIG.

    Example for a Second Stage Regulator

    1. Assume load of 250,000 BTU's per hour.
    2. Assume a minimum delivery pressure of 10" w.c.
    3. Assume a minimum inlet pressure of 10 PSIG.
    4. For these conditions, refer to chart for the LV4403B Series, Second Stage Regulator, shown below.
    5. Find the line on the chart corresponding to the anticipated inlet pressure.
    6. Draw a vertical line upward from the point of assumed load (250,000 BTU's per hour) to intersect with the line corresponding to the lowest inlet pressure.
    7. Read horizontally from the intersection of these lines to the delivery pressure at the left side of the chart. In this example the delivery pressure will read 10.6" w.c. Since the delivery pressure will be 10.6" w.c. at the maximum load condition and lowest anticipated inlet pressure, the regulator is sized properly for the demand.

    Second stage regulator delivery pressure PSIG.

    Download Our App

    Easily order new parts, easily locate our branches, and easily check your orders on the go. That’s the Tarantin App. Download it today.

    Apple DownloadGoogle Play Download

    Don’t have an online ordering account? CLICK HERE to sign up today.

    Location

    Address: 86 Vanderveer Road
    Freehold, NJ 07728

    Phone: 1 800.922.0724

    Fax: 1 732.780.5173

    Follow Us:

     

     

     

     

      

    facebook icon linkedin icon youtube icon